    Manual start device IPR 535 Gorizont "Start" MK is designed to start the actuating mechanisms of fire extinguishing systems, smoke removal systems, etc. Explosion protection marking 1Ex d IIB T6 Gb. Full compliance with the requirements of GOST 53325 as amended in 2012.

    The detector can be used as a single element, as well as in alarm loops (AL) for closing (parallel connection) or opening (series connection). Two-color status indicator: standby mode indication - green flashes with a period of 5-7 seconds; indication of the "alarm" mode - red flickering with a frequency of more than 5 Hz.

    Class according to GOST 53325-2012: manual detector - class A (activation by one action); manual start devices - class B (activation by two actions).

    Manual starter IPR 535 Gorizont "Start" is designed to start the actuating mechanisms of fire extinguishing systems, smoke removal systems, etc. The manual starter is designed for installation in hazardous areas of class 0 and below.

    Name IPR535 Horizon PUSK MK IPR535 Horizon PUSK
    Explosion protection marking 1Ex d IIB T6 Gb 0Ex ia IIB T6 Ga
    Marking of microprotection parameters   LI: 1 µH, CI: 30 pF, UI: 27 V, II: 25 mA, PI: 0.8 W
    Degree of protection of the shell IP67 IP67
    Operating temperature -60°C<Ta<75°C -60°C<Ta<70°C
    Climatic performance UHL1  
    Supply voltage 8-28V 8-28V
    Current consumption in standby mode, no more 80uA 80uA
    Own current consumption in the "Fire" mode, no more 0.7mA 0.7mA
    Maximum current of the external additional resistor circuit, no more 100mA 100mA
    Case color: yellow yellow
    Housing material Aluminium alloy High impact polyamide
    Dimensions without cable entries 131x122x46mm 134x108x46mm

    Selection table for additional resistors

    FACP type Connection options
    Parallel connection (make) Sequential connection (on opening)
    LB-07 Rd must ensure current consumption> 15 mA, Rd \u003d 11 kOhm, Rok \u003d 2 kOhm, VDok \u003d KD522.
    Rok \u003d 2 kOhm, VDok \u003d KD522.
    Ray Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A. Rd = 2.2 kOhm, Rok = 2.4 kOhm, VDok = KD521A.
    PPK-2 Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A. Rd = 10.0 kOhm, Rok = 3.6 kOhm, VDok = KD521A.
    fireball Rd \u003d 1.5 kOhm (3.0 kOhm - to determine double drawdown), Rd \u003d 8.2 kOhm (4.7 kOhm - to determine double drawdown),
    Rok \u003d 4.7 kOhm, do not install VDok Rok \u003d 4.7 kOhm, do not install VDok
    Yakhont-16i Rd \u003d 1.8 kOhm (4.0 kOhm - to determine double drawdown), Not applicable
    Rok = 8.2 kOhm, do not set VDok
    WERS Rd \u003d 820 Ohm (1.8 kOhm - to determine double drawdown), Rd \u003d 10 kOhm (4.7 kOhm - to determine double drawdown),
    Rok = 7.5 kOhm, do not set VDok Rok = 7.5 kOhm. Do not install VDoc

     

    AM - indicates the presence of a product modification with an address label.

    The IPR535 detector Horizont PUSK MK is supplied with cable glands of various designs:

    • for open laying of the attached cable (index in the designation - K );
    • for laying the attached cable in the pipe G1/2 ( T-1/2 );
    • for laying the attached cable in the pipe G3/4 ( T-3/4 );
    • for connecting an armored cable ( B );
    • for connecting a cable in a metal hose RZTSH-15mm or 20mm ( KM15, KM20 ).


    The detector IPR535 Horizon PUSK is supplied with two cable glands, which allow the detector to be installed in an alarm loop with a round cable with a diameter of 6-10mm.