UDP IPR535 HORIZON EMERGENCY EXIT MK

UDP IPR535 HORIZON EMERGENCY EXIT MK
Price: 10 198 RUB
Type of protection:
  • (0ExiaIIBT6Ga)
  • MK (1ExdIIBT6Gb)
You choosed:

    IPR 535 Horizon "Emergency exit" MK is designed to unblock emergency exits.Explosion protection marking 1Ex d IIB T6 Gb.

    IPR 535 Horizon "Emergency exit" is designed to unblock emergency exits and is intended for installation in hazardous zones of class 0 and below.

    Explosion protection marking 1Ex d IIB T6 Gb
    Degree of protection of the shell IP67
    Operating temperature -60C<Ta<75C
    Climatic performance UHL1
    Supply voltage 8-28V
    Current consumption in standby mode, no more 80uA
    Own current consumption in the "Fire" mode, no more 0.7mA
    Maximum current of the external additional resistor circuit, not more than 100mA
    Case color: green
    Housing material Aluminium alloy
    Dimensions without cable entries 131x122x46mm

    Selection table for additional resistors

    FACP type Connection options
    Parallel connection (make) Sequential connection (on opening)
    LB-07 Rd must ensure current consumption> 15 mA, Rd \u003d 11 kOhm, Rok \u003d 2 kOhm, VDok \u003d KD522.
    Rok \u003d 2 kOhm, VDok \u003d KD522.
    Ray Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A. Rd = 2.2 kOhm, Rok = 2.4 kOhm, VDok = KD521A.
    PPK-2 Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A. Rd = 10.0 kOhm, Rok = 3.6 kOhm, VDok = KD521A.
    fireball Rd \u003d 1.5 kOhm (3.0 kOhm - to determine double drawdown), Rd \u003d 8.2 kOhm (4.7 kOhm - to determine double drawdown),
    Rok \u003d 4.7 kOhm, do not install VDok Rok \u003d 4.7 kOhm, do not install VDok
    Yakhont-16i Rd \u003d 1.8 kOhm (4.0 kOhm - to determine double drawdown), Not applicable
    Rok = 8.2 kOhm, do not set VDok
    WERS Rd \u003d 820 Ohm (1.8 kOhm - to determine double drawdown), Rd \u003d 10 kOhm (4.7 kOhm - to determine double drawdown),
    Rok = 7.5 kOhm, do not set VDok Rok = 7.5 kOhm. Do not install VDoc

     

    AM - indicates the presence of a product modification with an address label.

    The detector IPR535 Horizon Emergency exit MK is supplied with cable glands of various designs:

      • for open laying of the attached cable (index in the designation - K );
      • for laying the attached cable in the pipe G1/2 ( T-1/2 );
      • for laying the attached cable in the pipe G3/4 ( T-3/4 );
      • for connecting an armored cable ( B );
      • for connecting a cable in a metal hose RZTSH-15mm or 20mm ( KM15, KM20 ).

    The detector IPR535 Horizon Emergency exit MK is supplied with two cable glands, which allow you to install the detector in an alarm loop with a round cable with a diameter of 6-10mm.