The board is designed to provide the ability to transmit light (text or symbol) alarm signals in fire alarm and fire extinguishing systems when working together with control and monitoring devices.
| Name of the equipment | Sphere VZ (Set 1) | Sphere VZ (Set 2) | Sphere VZ (Set 3) | Sphere VZ (Set 4) |
| Power supply from a DC source with voltage | =12-30 V | =12-30 V | =12-30 V | |
| Maximum current consumption | 0.15 A | 0.25 A | 0.25 A | |
| Power supply from an AC source with voltage | ~220 V | ~220 V | ~220 V | |
| Maximum current consumption | 0.05 A | 0.24 A | 0.18 A | |
| Type and level of explosion protection of the alarm | 1 Ex mb ib IIC T5 Gb X/Ex tb ib IIIC T100°C Db X | |||
| Degree of protection of the shell | IP 65 | |||
| Overall dimensions | 385x165x55 mm | |||
| Inscription size | Not less than 330x80 mm | |||
| Sound pressure at a distance of 1.00 m | Not less than 105±5 dB | |||
| Battery life | At least 5 hours | |||
| The alarm light signal of the alarm device is clearly visible when illuminated (the alarm device) | Up to 500 lux | |||
| Weight | No more than 2.5 kg | |||
| Temperature range | -60°С…+85°C | -40°С…+60°C | ||
| Material | Impact-resistant polyamide | |||
The alarm is supplied with a power cable in a 1.5 m long metal sleeve or at the customer’s request. To carry out installation, there is a coupling at the end of the alarm power cable, which is screwed onto the cable entry of the junction box with a G 1/2 thread.