MANUAL CALLS IP512 HORIZONT OP-N

MANUAL CALLS IP512 HORIZONT OP-N
Price on request
Equipment:
  • Request a price from the manager
You choosed:

    Manual fire detectors and remote start devices comply with the requirements of TR EAEU 043/2017, GOST R 53325-2012.

    Manual fire detectors of the IP 512 HORIZONT OP-N series are manufactured in two versions with an addressable expander IP 512-451.5-A-HORIZONT OP-AM-N and without it (without an address label) IP 512-451.4-A-HORIZONT OP-N and are used to manually trigger a fire alarm.

    Remote start devices of the UDP 512 HORIZONT "PUSK" OP - N series are manufactured in two versions with an address expander UDP 512 - 451.7 - V - HORIZONT "PUSK" OP-AM - N and without it (without an address label) UDP 512 -451.6 - V - HORIZONT "PUSK" OP - N and are components of a block-modular PPU, designed for manual start of fire extinguishing systems, smoke removal, etc.

    UDP 512 series remote starters UDP 512 HORIZON EMERGENCY EXIT OP-N are manufactured in two versions with address expander UDP 512-451.19-A-HORIZON EMERGENCY EXIT OP-AM and without it (without address label) UDP 512-451.18 - A - HORIZON "EMERGENCY EXIT" OP - N and are components of a block-modular PPU designed to unlock emergency exits.

    Equipment with an individually assigned address interacts with the S2000-AP1 version 2 address expander manufactured by Bolid LLC. The address version of the detector is used with the two-wire communication line controller "S2000-KDL" or "S2000-KDL-2I" as part of the integrated security system "Orion". https://bolid.ru/ .

    Case material of IPR and UDP is corrosion-resistant stainless steel.

    IPR, UDP is equipped with two cable glands of the KV, KV series TU 27.33.13-359-81888935-2019. Connecting thread of cable glands M20x1.5. Cable glands allow you to enter and exit round cables of various diameters:

    • for open laying of the attached cable (index in the designation - K);
    • for laying the attached cable in a pipe with an internal or external thread G1 / 2 or M20x1.5 (TV1 / 2, TH1 / 2, TV20, TH20);
    • for connecting an armored cable with a double seal (B)
    • for connecting a cable in a metal hose RZTSH-10mm, RZTSKh-12mm, RZTSKh-15mm or RZTSKh-20mm (KM10, KM12, KM15, KM20).

    General industrial manual fire detectors and remote start devices have differences in marking, because differ in purpose.

    IP 512-451.4 - A - HORIZON OP - NManual fire detector class A (one-action activation) with addressless design
    IP 512-451.5 - A - HORIZON OP-AM - NManual fire detector class A (one-action activation) with addressable design
    UDP 512-451.6 - V - HORIZON "START" OPClass B remote starter (two-action activation) with non-addressed version
    UDP 512-451.7 - V - HORIZON "START" OP-AM - NClass B remote starter (two-action activation) with addressable version
    UDP 512-451.18 - A - HORIZON "EMERGENCY EXIT" OP - NClass A remote starter (single-action activation) with non-addressed version
    UDP 512-451.19 - A - HORIZON "EMERGENCY EXIT" OP-AM - NClass A remote starter (single-action activation) with addressable design
     IP 512-451.4 - A - HORIZON OP - NUDP 512-451.6 - V - HORIZON "START" OPUDP 512-451.18 - A - HORIZON "EMERGENCY EXIT" OP - N
     IP 512-451.5 - A - HORIZON OP-AM - NUDP 512-451.7 - V - HORIZON "START" OP-AM - NUDP 512-451.19 - A - HORIZON "EMERGENCY EXIT" OP-AM - N
    Case colorRedYellowGreen
    MaterialStainless steel
    Activation class according to GOST 53325A
    (one action)
    B
    (two actions)
    A
    (one action)
    Ambient temperature-60°С … +75°С
    Degree of protection of the shellIP66/67
    Rated supply voltage12V - 24V
    Own current consumption, no more
    Non-address execution:
    • in standby mode
    • in fire mode
    Address execution:
    • in standby mode
    • in fire mode

     

    300uA
    1.2mA

     

    23mA
    20mA

    Maximum allowable current in alarm mode, no more100mA
    The maximum allowable switching current on the relay contacts, no more2A
    The maximum allowable voltage on the relay contacts, no more250V
    Overall dimensions, mm, no more (* without cable glands)113*х109х86

    Designation when ordering:

    X 1 -X 2 -X 3 -X 4
    1234

     

    1. Type, number and version of the device (see Table 1):
      IP 512-451.4 - A - HORIZON OP;
      IP 512-451.5 - A - HORIZON OP-AM;
      UDP 512-451.6 - V - HORIZON "START" OP;
      UDP 512-451.7 - V - HORIZON "START" OP-AM;
      UDP 512-451.18 - A - HORIZON "EMERGENCY EXIT" OP;
      UDP 512-451.19 - A - HORIZON "EMERGENCY ENTRANCE" OP-AM.
    2. Body material:
      H - stainless steel;
    3. Cable gland type:
      K - for open cable laying with a diameter of 6.5-13.9 mm;
      TV1 / 2 (TV20) - for laying a cable with a diameter of 6.5-13.9 mm in a pipe with a connecting internal thread G1 / 2 or M20x1.5;
      ТН1/2 (ТН20) - for laying a cable with a diameter of 6.5-13.9 mm in a pipe with a connecting external thread G1/2 or M20x1.5;
      B - for laying with double sealing of an armored cable with an outer part with a diameter of 15.0-21.0 mm and an inner sheath diameter of 6.5-13.9 mm;
      KM10 - for laying a cable with a diameter of 3.1-8.6 mm in the RZTsH-10 metal hose;
      KM12 - for laying a cable with a diameter of 3.1-8.6 mm in the RZTsH-12 metal hose;
      KM15 - for laying a cable with a diameter of 6.1-11.7 mm in the RZTsH-15 metal hose;
      KM20 - for laying a cable with a diameter of 6.5-13.9 mm in the RZTsH-20 metal hose.
    4. Designation of climatic version according to GOST:
      HL - for macroclimatic regions with a cold climate;
      UHL - for macroclimatic regions with a temperate and cold climate;
      OM - for macroclimatic regions with both temperate cold and tropical maritime climates, including ships with an unrestricted navigation area.