IP 101 AZIMUT

IP 101 AZIMUT
Price on request
Equipment:
  • Request a price from the manager
You choosed:

    The IP101 Azimuth MK detector is included in the alarm loop without additional current-limiting elements (there is a built-in 2kOhm resistor) and without regard to polarity.Alarm notification is provided by an increase in the current through the detector, and by turning on the indicator.

    The threshold temperature of response corresponds to the classes A3 [64 ... 76 ° C], C [84 ... 100 ° C], D [99 ... 115 ° C].

    The IP101 Azimuth detector is used to detect the source of fire and transmit a signal to the receiving and control device and is designed to work as part of automatic fire extinguishing and fire alarm systems at special-purpose facilities.The detector is designed for installation in hazardous areas of class 0 and below.The detector is available in versions with a conventional (for tanks) or shortened (for rooms) thermosensitive housing part.
    There are three normal values for the threshold temperature: 70 ° C; 90 ° C; 110 ° C.

    Name IP101 Azimuth MK IP101 Azimuth
    Explosion protection marking 1 Ex d IIB T4 Gb 0Ex ia IIB T6 Ga
    I.S. parameter labeling   LI: 1 µH, CI: 1000 pF, UI: 27 V, II: 13 mA, PI: 0.4 W
    Degree of protection of the shell IP67 IP67
    Operating temperature range, °С -60...+115 -60...+85
    Supply voltage range, V 6...27 6...27
    Current consumption in standby mode at a supply voltage of 24 V: 0.35 mA 0.35 mA
    Own current consumption in the "Fire" mode, no more 2.3 mA. 2.3 mA.
    Ready time after supply voltage no more than 0.5 sec. no more than 0.5 sec.
    Overall dimensions, mm - excluding cable glands - 113x1000x162; - regular - 122x82x152
    - elongated - 122x82x259

    Selection table for additional resistors

    FACP type Connection options
    Parallel connection (make)
    LB-07 Rd must ensure current consumption> 15 mA,
    Rok \u003d 2 kOhm, VDok \u003d KD522.
    Ray Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A.
    PPK-2 Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A.
    fireball Rd \u003d 1.5 kOhm (3.0 kOhm - to determine double drawdown),
    Rok \u003d 4.7 kOhm, do not install VDok
    Yakhont-16i Rd \u003d 1.8 kOhm (4.0 kOhm - to determine double drawdown),
    Rok = 8.2 kOhm, do not set VDok
    WERS Rd \u003d 820 Ohm (1.8 kOhm - to determine double drawdown),
    Rok = 7.5 kOhm, do not set VDok

     

    AM - indicates the presence of a product modification with an address label.

    The response temperature set by the manufacturer can be changed by the consumer by installing an appropriate resistor in the detector terminals. The detector is equipped with resistors to set the response temperature: 70°С; 90°C; 110°C.
    The dependence of the operating temperature of the IP Azimuth MK on the resistance of the setting resistor.

    T, °C 51 60 70 81 90 100 110 135 150
    Rt, kOhm thirty 20 13 8.2 5.6 3.6 2.4 0.560 0

    The IP101 Azimuth MK detector is supplied with cable glands of various designs:

    • for open laying of the connected cable with a diameter of 8-12 mm (index in the designation - K);
    • for laying the attached cable in the G1/2 pipe;
    • for laying the attached cable in a G3/4 pipe;
    • for connecting an armored cable with a diameter of 8-12mm.


    Dependence of the operating temperature of the IP Azimuth on the resistance of the setting resistor.

    T, °C 51 60 70 81 90 100 110
    Rt, kOhm thirty 20 13 8.2 5.6 3.6 2.4

    The IP101 Azimuth detector is supplied with two cable glands, which allow the detector to be installed in an alarm loop with a round cable with a diameter of 6-10mm.