FLAME DETECTOR IP329/IP330 TELOS ModBus

FLAME DETECTOR IP329/IP330 TELOS ModBus
Price: 126 227 RUB
Type of protection:
  • VZ (0ExiaIIBT6Ga)
  • MK (1ExdIIBT6Gb)
You choosed:

    The detector is designed to detect fires accompanied by the appearance of electromagnetic radiation simultaneously in the ultraviolet and infrared spectral ranges and to send a "Fire" notification to the control panel.The use of the IR and UV parts of the spectrum eliminates false alarms of the detector.The detector meets the requirements of GOST R 53325-2012.The detector is used in installations for fire protection of buildings, structures, premises and equipment in open areas.

    Effective for harsh climatic conditions (-60 ... + 75 C °), including the regions of the Far North (heating of the internal volume).They work with control and monitoring devices, addressable fire alarm systems, complex integrated safety management systems and automatic fire extinguishing systems of all leading Russian and foreign manufacturers.The detector meets the requirements of GOST R 53325-2012.

    The list of typical production premises, technological processes, for the protection of which the product is used:

    • Industrial buildings with production and storage:
      wood products, synthetic resins, synthetic fibers, polymeric materials, textile, textile haberdashery, clothing, footwear, leather, tobacco, fur and pulp and paper products, celluloid, rubber, rubber products, combustible X-ray and film films, cotton, varnishes, paints , solvents, flammable liquids, flammable liquids, lubricants, chemical reagents, alcoholic beverages, alkali metals, metal powders, flour, compound feed, other products and materials emitting dust;
    • Industrial buildings with production:
      paper, cardboard, wallpaper, livestock and poultry products;
    • Industrial buildings with storage:
      non-combustible materials in combustible packaging, solid combustible materials;
    • Special structures:
      premises of car service enterprises;
    • Administrative, domestic and public buildings and structures:
      artistic, wardrobe, restoration workshops, cinema and light projection, hardware, photo laboratories, premises of museums and exhibitions.

    Support for the 485 Modbus protocol allows the detector to be used both in security and fire alarm systems and in automated process control systems.Connection to digital and analogue networks is possible.Diagnostics and configuration of devices can be carried out remotely for ease of maintenance at remote, low-maintenance infrastructure facilities.Registration and archiving of all events occurs automatically, the results are saved in the system.

    The detectors are manufactured in versions that differ in the type of explosion protection and housing material (see.(see table 1 in the "Characteristics" tab).Explosion protection types: "flameproof enclosure" d "" and "intrinsically safe electrical circuit" ia "". Explosion protection marking, respectively: 1Ex d IIC T6 Gb X / Ex tb IIIC T85 ° C Db X and 0Ex ia IIC T6 Ga X / Ex ia IIIC T85 ° C Da X according to GOST R IEC 60079-0-2011.The "X" mark in the marking means: do not expose the light-transmitting part to mechanical stress.Body material: aluminum alloy; Cink Steel; stainless steel.

    For the version "intrinsically safe electrical circuit" ia "" marking of explosion protection parameters: "Li: 1mkHn, Ci: 1000pF, Ui: 28B, Ii: 70mA, Pi: 2W" according to GOST R IEC 60079-11-2011.

    The detector can be installed in hazardous areas of premises and outdoor installations according to the classification of GOST IEC 60079-10-1-2011 and other directive documents regulating the use of electrical equipment in hazardous areas.The environment may contain explosive mixtures of gases and vapors with air, categories IIA and IIB.

    The detector is designed for operation at ambient temperatures from minus 60 ° С to plus 75 ° С, type of climatic modification UHL1 in accordance with GOST 15150-69.The degree of protection of the shell is IP67 in accordance with GOST 14254.Placement category 1 according to GOST 15150-69

    Versions of detectors series IP329 / 330 Telos

    Table 1.

    Designation Body material Explosion protection type
    IP329 / 330-310.3-1 Telos MK-S Modbus RS485 Cink Steel PB Ex d I Mb X / 1Ex d IIС T6 Gb X / Ex tb IIIC T85 ° C Db X
    IP329 / 330-310.3-1 Telos MK-N Modbus RS485 Stainless steel PB Ex d I Mb X / 1Ex d IIС T6 Gb X / Ex tb IIIC T85 ° C Db X
    IP329 / 330-310.2-1 Telos VZ-N Modbus RS485 Stainless steel PO Ex ia I Ma X / 0Ex ia IIC T6 Ga X / Ex ia IIIC T85 ° C Da X
    IP329 / 330-310.3-1 Telos MK-A Modbus RS485 Aluminium alloy PB Ex d I Mb X / 1Ex d IIС T6 Gb X / Ex tb IIIC T85 ° C Db X
    IP329 / 330-310.2-1 Telos VZ-A Modbus RS485 Aluminium alloy PO Ex ia I Ma X / 0Ex ia IIC T6 Ga X / Ex ia IIIC T85 ° C Da X

    Table 2.

    Characteristic Meaning
    Spectral sensitivity, nm IR 4300
    Uv 185 - 260
    Detection range of test foci, m, not less TP-5 (N-heptane) 25
    TP-6 (ethyl alcohol) 25
    Viewing angle, gr IR 90
    Uv 90
    Response time, no more, sec   ten
    Direct light resistance, not less lux incandescent lamps 250
    fluorescent lamps 2500
    Resistance to optical radiation in the visible range of the spectrum, no more, lux 80,000
    Supply voltage, V 8 - 28
    Consumption current, no more, mA without heating twenty
    heated 200
    Characteristics of the Sh1 and Sh2 optocoupler relays maximum voltage, V, not more 100
    maximum current, mA, not more 100
    open resistance, Ohm, no more 16
    isolation voltage, V, not less 1500
    Ready time after power supply, no more, sec 45
    Diameter of the cable to be inserted, mm 6 - 12
    Section of the connected conductors, mm 2 0.35 - 1.5
    Operating temperature range, С -60 ° C .. + 75 ° C
    Sheath protection IP67
    Climatic performance UHL1
    Overall dimensions, mm 334x271x116
    Weight, no more, kg 3.5kg

    An example of a detector designation when ordering:

    IP330 / IP329 Telos MK - WITH - Modbus RS485 - Kv
    1 2 3 4 5

     

    1. type of device;
    2. explosion protection designation:
      • MK - PB Ex d I Mb X / 1Ex d IIС T6 Gb Х / Ex tb IIIC T85 ° C Db X;
      • ВЗ - PO Ex ia I Ma X / 0Ex ia IIC T6 Ga X / Ex ia IIIC T85 ° C Da X
    3. Case material:
      • A - aluminum alloy;
      • C - galvanized steel;
      • H - stainless steel;
    4. Availability of the Modbus RS485 communication protocol;
    5. Type designation of cable glands:
      • K - for open laying of cables with a diameter of 6.5-13.9 mm;
      • B - for an armored cable with a through diameter of 6.5-13.9 mm;
      • Т-1/2 - for laying a cable with a diameter of 6.5-13.9 mm in a pipe with a connecting thread G1 / 2;
      • Т-3/4 - for laying a cable with a diameter of 6.5-13.9 mm in a pipe with a connecting thread G3 / 4;
      • KM10 - for a cable with a diameter of 3.1-8.6 mm in a metal hose RZTsKh-10mm;
      • KM12 - for a cable with a diameter of 3.1-8.6 mm in a metal hose RZTsKh-12mm;
      • KM15 - for a cable with a diameter of 6.1-11.7 mm in a metal hose RZTsKh-15mm;
      • KM20 - for a cable with a diameter of 6.5-13.9 mm in a metal hose RZTsKh-20mm.